Genuine loop-powered flowmeter for minimized cost of ownership. Accurate measurement of liquids and gases for a wide range of standard applications.
Sensor features
Cost‐effective – multi‐purpose device; an alternative to conventional volumetric flowmeters. Fewer process measuring points – multivariable measurement (flow, density, temperature). Space‐saving installation – no in-/outlet run needs. Compact dual-tube sensor. std_successorproducts_product_differentiating_tech_features_7694_1530102815. Process pressure up to 100 bar (1450 psi).
Transmitter features
Convenient device wiring – separate connection compartment. Safe operation – no need to open the device due to display with touch control, background lighting. Integrated verification – Heartbeat Technology. Loop-powered technology. Robust dual-compartment housing. Plant safety: worldwide approvals (SIL, Haz. area).
Mass flow, density, temperature, volume flow, corrected volume flow, reference density
Maksymalny błąd pomiaru
Mass flow (liquid): ±0.25 % Volume flow (liquid): ±0.25 % Mass flow (gas): ±0.75 % Density (liquid): ±0.0005 g/cm³
Zakres pomiarowy
0 to 70 000 kg/h (0 to 2570 lb/min)
Maks. ciśnienie procesu
PN 100, Class 600, 63K
Zakres temperatury medium
–40 to +140 °C (–40 to +284 °F)
Temperatura otoczenia
–40 to +60 °C (–40 to +140 °F)
Materiał obudowy czujnika
1.4301 (304), corrosion resistant
Materiał obudowy przetwornika
AlSi10Mg, coated
Stopień ochrony
IP66/67, type 4X enclosure
Wyświetlacz
4‐line backlit display with touch control (operation from outside) Configuration via local display and operating tools possible Remote display available
Wyjścia
4‐20 mA HART (passive) 4‐20 mA (passive) Pulse/frequency/switch output (passive)
Wejścia
None
Komunikacja cyfrowa
HART, PROFIBUS PA, FOUNDATION Fieldbus
Zasilacz
DC 18 to 35 V (4‐20 mA HART with/without pulse/frequency/switch) DC 18 to 30 V (20 mA HART, 4‐20 mA) DC 9 to 32 V (PROFIBUS PA)
Dopuszczenia do stosowania w strefach zagrożonych wybuchem
ATEX, IECEx, cCSAus, NEPSI, INMETRO
Inne certyfikaty i dopuszczenia
3.1 material, calibration performed on accredited calibration facilities (acc. to ISO/IEC 17025), NAMUR, SIL, PED, CRN, 3-A
Product safety
Functional safety according to IEC 61508, applicable in safety-relevant applications in accordance with IEC 61511
Metrological approvals and certificates
Calibration performed on accredited calibration facilities (acc. to ISO/IEC 17025)
Pressure approvals and certificates
PED, CRN
Material certificates
3.1 material
Hygienic approvals and certificates
3-A
Product headline
Genuine loop-powered flowmeter for minimized cost of ownership. Accurate measurement of liquids and gases for a wide range of standard applications.
Sensor features
Cost‐effective – multi‐purpose device; an alternative to conventional volumetric flowmeters. Fewer process measuring points – multivariable measurement (flow, density, temperature). Space‐saving installation – no in-/outlet run needs. Compact dual-tube sensor. std_successorproducts_product_differentiating_tech_features_7694_1530102815. Process pressure up to 100 bar (1450 psi).
Transmitter features
Convenient device wiring – separate connection compartment. Safe operation – no need to open the device due to display with touch control, background lighting. Integrated verification – Heartbeat Technology. Loop-powered technology. Robust dual-compartment housing. Plant safety: worldwide approvals (SIL, Haz. area).
Mass flow, density, temperature, volume flow, corrected volume flow, reference density
Maksymalny błąd pomiaru
Mass flow (liquid): ±0.25 % Volume flow (liquid): ±0.25 % Mass flow (gas): ±0.75 % Density (liquid): ±0.0005 g/cm³
Zakres pomiarowy
0 to 70 000 kg/h (0 to 2570 lb/min)
Maks. ciśnienie procesu
PN 100, Class 600, 63K
Zakres temperatury medium
–40 to +140 °C (–40 to +284 °F)
Temperatura otoczenia
–40 to +60 °C (–40 to +140 °F)
Materiał obudowy czujnika
1.4301 (304), corrosion resistant
Materiał obudowy przetwornika
AlSi10Mg, coated, 1.4404 (316L)
Stopień ochrony
IP66/67, type 4X enclosure
Wyświetlacz
4‐line backlit display with touch control (operation from outside) Configuration via local display and operating tools possible Remote display available
Wyjścia
4‐20 mA HART (passive) 4‐20 mA (passive) Pulse/frequency/switch output (passive)
Wejścia
None
Komunikacja cyfrowa
HART, PROFIBUS PA, FOUNDATION Fieldbus
Zasilacz
DC 18 to 35 V (4‐20 mA HART with/without pulse/frequency/switch) DC 18 to 30 V (20 mA HART, 4‐20 mA) DC 9 to 32 V (PROFIBUS PA)
Dopuszczenia do stosowania w strefach zagrożonych wybuchem
ATEX, IECEx, cCSAus, NEPSI, INMETRO
Product safety
CE, C-Tick, EAC marking
Functional safety
Functional safety according to IEC 61508, applicable in safety-relevant applications in accordance with IEC 61511
Metrological approvals and certificates
Calibration performed on accredited calibration facilities (acc. to ISO/IEC 17025)
Używamy plików cookie, aby poprawić komfort przeglądania, gromadzić dane statystyczne w celu optymalnego działania witryny i wyświetlać spersonalizowane reklamy lub treści.
Wybierając "Akceptuj wszystko", wyrażacie Państwo zgodę na używanie plików cookie.
Aby uzyskać więcej informacji, prosimy o zapoznanie się z naszą Polityką plików cookie .